EASY-E4-AC-8RE1Модуль ввода / вывода 100/240V AC/DC, 4DI, 4DO реле 5А
Основные характеристики
| Product range | Control relays easyE4 |
| Subrange | easyE4 digital input/output enhancements |
| Basic function | easyE4 extensions |
| Description | Input/output extension for easyE4 control relayExpandable with the easyE4 series of digital input/output expansions with easy-E4-CONNECT1 connector (Item Y7-197225)Rated operating voltage 100 to 240 VAC or 100 to 240 VDC (cULus: 100 to 110 VDC)Digital inputs: 8Digital outputs: 8 relaysScrew terminals |
| Inputs | |
| Inputs expansion (number) | digital: 8 |
| Additional features | |
| Display | with diagnostic LED |
| Software | EASYSOFT-SWLIC/easySoft 7 |
| Supply voltage | 100 - 240 V AC, 100 - 240 V DC (cULus: 100 - 110 V DC) |
| For use with | easyE4 |
| General | |
| Standards | EN 61000-6-2EN 61000-6-3IEC 60068-2-6IEC 60068-2-27IEC 60068-2-30IEC 61131-2EN 61010EN 50178 |
| ApprovalsApprovals | cULus |
| Approvalscertificate | CE |
| Dimensions (W x H x D) | 71.5 x 90 x 58 mm |
| Weight | 0.232 kg |
| Mounting | Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories) |
| Connection type | Screw terminal |
| Terminal capacities | |
| Screw terminalsSolid | 0.2 - 4 mm2 |
| Screw terminalsflexible | 0.2 - 2.5 mm2 |
| Screw terminalsSolid or flexible conductor, with ferrule | 0,2 - 2,5 mm2 |
| Screw terminalsSolid or stranded | 22 - 12 AWG |
| Screw terminalsStandard screwdriver | 0.8 x 3.5 mm |
| Screw terminalsTightening torque | 0.5 - 0.7 Nm |
| Screw terminalsStripping length | 6.5 мм |
| Climatic environmental conditions | |
| Operating ambient temperature | -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C |
| Condensation | Take appropriate measures to prevent condensation |
| Storage [ϑ] | -40 - +70 °C |
| relative humidity | in accordance with IEC 60068-2-30, IEC 60068-2-785 - 95 % |
| Air pressure (operation) | 795 - 1080 hPa |
| Ambient conditions, mechanical | |
| Protection type (IEC/EN 60529, EN50178, VBG 4) | IP20 |
| Vibrations | In accordance with IEC 60068-2-6constant amplitude 0.15 mm: 10 - 57constant acceleration 2 g: 57 - 150 Hz |
| Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms | 18 Impacts |
| Drop to IEC/EN 60068-2-31 [Drop height] | 50 мм |
| Free fall, packaged (IEC/EN 60068-2-32) | 0.3 m |
| Mounting position | Vertical or horizontal |
| Electromagnetic compatibility (EMC) | |
| Overvoltage category/pollution degree | III/2 |
| Electrostatic discharge (ESD)applied standard | according to IEC EN 61000-4-2 |
| Electrostatic discharge (ESD)Air discharge | 8 kV |
| Electrostatic discharge (ESD)Contact discharge | 6 kV |
| Electromagnetic fields (RFI) to IEC EN 61000-4-3 | 0.8 - 1.0 GHz: 101.4 - 2 GHz: 32.0 - 2.7 GHz: 1 V/m |
| Radio interference suppression | EN 61000-6-3 Class B |
| Burst | according to IEC/EN 61000-4-4Supply cables: 2Signal cables: 2 kV |
| power pulses (Surge) | according to IEC/EN 61000-4-51 kV (supply cables, symmetrical)2 kV (supply cables, asymmetrical) |
| Immunity to line-conducted interference to (IEC/EN 61000-4-6) | 10 V |
| Insulation resistance | |
| Clearance in air and creepage distances | nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
| Insulation resistance | in accordance with EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
| Power supply | |
| Rated operational voltage [Ue] | 100 - 240V DC (-15/+10%)100 - 240 DC (cULus: 100 -110 DC) (-15/+10%) V |
| Permissible range [Ue] | 85 - 264 V AC85 - 264 V DC (cULus: 85 - 120 V DC) |
| Residual ripple | ≦ 5 % |
| Siemens MPI, (optional) | yes |
| Frequency | 50/60 (± 5%) Hz |
| Voltage dips | ≤ 20 ms at 100V AC10 ms at 100V DC ms |
| Fuse | ≧ 1A (T) A |
| Power loss [P] | Normally 11 W |
| Digital inputs 115/230 V AC | |
| Number | 8 |
| Potential isolation | from power supply: nobetween inputs: nofrom the outputs: yesto the base unit: yesto the expansion units: yes |
| Rated operational voltage [Ue] | 100 - 240 V AC100 - 240 V DC (cULus: 100 - 110 V DC) V |
| Input voltage [Ue] | Condition 0: 0 - 40V AC/DCCondition 1: 79–264 V AC/DC (cULus: 79–264 V AC/79–120 V DC) V |
| Rated frequency | 50/60 Hz |
| Input current at signal 1 | I1 - I8: 8 x 0.25 (at 115V AC, 60 Hz)I1 - I8: 8 x 0.5 (at 230V AC, 50 Hz)I1 - I8: 8 x 0.25 (at 115V DC)I1 - I8: 8 x 0.5 (at 230V DC) mA |
| Deceleration time | type 39⁄32 (0 - > 1/1 -> 0, 50/60Hz) in ACtype 0.5 (0 - > 1/1 -> 0) in DC ms |
| Cable length | 40 (unshielded) m |
| Relay outputs | |
| Number | 8 |
| Outputs in groups of | 1 |
| Parallel switching of outputs for increased output | Not permitted |
| Protection of an output relay | B16 circuit breaker or 8 A (T) fuse |
| Potential isolation | Safe isolation according to EN 50178: 300 V ACBasic isolation: 600 V ACfrom power supply: yesFrom the inputs: yesbetween outputs: yesto expansion devices: yes |
| ContactsConventional thermal current (10 A UL) | 5 A |
| ContactsRecommended for load: 12 V AC/DC | > 500 mA |
| ContactsRated impulse withstand voltage Uimp of contact coil | 6 kV |
| ContactsRated operational voltage [Ue] | 240 V AC |
| Rated insulation voltage [Ui] | 240 V AC |
| Safe isolation according to EN 50178 | 300 between coil and contact300 between two contacts V AC |
| Making capacityAC–-15, 250 V AC, 3 A (600 ops./h) [Operations] | 300000 |
| Making capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations] | 200000 |
| Breaking capacity AC-15, 250 V AC, 3 A (600 Ops./h) [Operations] | 300000 |
| Breaking capacity DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations] | 200000 |
| Filament bulb load1000 W at 230/240 V AC [Operations] | 25000 |
| Filament bulb load500 W at 115/120 V AC [Operations] | 25000 |
| Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACWith upstream electrical device [Operations] | 25000 |
| Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACUncompensated [Operations] | 25000 |
| Fluorescent lamp loadFluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations] | 25000 |
| Switching frequencyMechanical operations | 10 x 106 |
| Switching frequencySwitching frequency | 10 Hz |
| Switching frequencyResistive load/lamp load | 2 Hz |
| Switching frequencyInductive load | 0.5 Hz |
| UL/CSAUninterrupted current at 240 V AC | 5 A |
| UL/CSAUninterrupted current at 24 V DC | 5 A |
| UL/CSAACControl Circuit Rating Codes (utilization category) | B 300 Light Pilot Duty |
| UL/CSAACMax. rated operational voltage | 300 V AC |
| UL/CSAACmax. thermal continuous current cos ϕ = 1 at B 300 | 5 A |
| UL/CSAACmax. make/break cos ϕ ≠ capacity 1 at B 300 | 3600/360 VA |
| UL/CSADCControl Circuit Rating Codes (utilization category) | R 300 Light Pilot Duty |
| UL/CSADCMax. rated operational voltage | 300 V DC |
| UL/CSADCMax. thermal uninterrupted current at R 300 | 1 A |
| UL/CSADCMax. make/break capacity at R 300 | 28/28 VA |
| Supply voltage UAux | |
| Power loss [P] | 11 W |
| Technical data for design verification | |
| Operating ambient temperature min. | -25 °C |
| Operating ambient temperature max. | +55 °C |
| IEC/EN 61439 design verification | |
| 10.2 Strength of materials and parts10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2 Strength of materials and parts10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2 Strength of materials and parts10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of ASSEMBLIES | Meets the product standard's requirements. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9 Insulation properties10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9 Insulation properties10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| PLC's (EG000024) / Logic module (EC001417) | |
| Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / Logic module (ecl@ss10.0.1-27-24-22-16 [AKE539014]) | |
| Supply voltage AC 50 Hz | 85 - 264 V |
| Supply voltage AC 60 Hz | 85 - 264 V |
| Supply voltage DC | 85 - 264 V |
| Voltage type of supply voltage | AC/DC |
| Switching current | 5 A |
| Number of analogue inputs | |
| Number of analogue outputs | |
| Number of digital inputs | 8 |
| Number of digital outputs | 8 |
| With relay output | Yes |
| Number of HW-interfaces industrial Ethernet | |
| Number of interfaces PROFINET | |
| Number of HW-interfaces RS-232 | |
| Number of HW-interfaces RS-422 | |
| Number of HW-interfaces RS-485 | |
| Number of HW-interfaces serial TTY | |
| Number of HW-interfaces USB | |
| Number of HW-interfaces parallel | |
| Number of HW-interfaces Wireless | |
| Number of HW-interfaces other | 2 |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for MODBUS | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Radio standard UMTS | No |
| IO link master | No |
| Redundancy | No |
| With display | No |
| Degree of protection (IP) | IP20 |
| Basic device | No |
| Expandable | Yes |
| Expansion device | Yes |
| With timer | No |
| Rail mounting possible | Yes |
| Wall mounting/direct mounting | Yes |
| Front build in possible | No |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| Category according to EN 954-1 | |
| SIL according to IEC 61508 | None |
| Performance level acc. EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Appendant operation agent (Ex ib) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |
| Width | 71.5 мм |
| Height | 90 мм |
| Depth | 58 мм |
| UL File No. | E205091 |
| UL Category Control No. | NRAQ/7 |
| North America Certification | UL listed |
| Degree of Protection | IEC: IP20, UL/CSA Type: - |
На этой странице вы можете приобрести Eaton Модуль ввода / вывода 100/240V AC/DC, 4DI, 4DO реле 5А (артикул: 0000197221). Мы рекомендуем внимательно изучить представленные технические характеристики и ознакомиться с официальными брошюрами от Eaton, чтобы выбрать товар в нужной конфигурации.
Для покупки модели EASY-E4-AC-8RE1 просто нажмите кнопку «В корзину» и перейдите в корзину для оформления заказа. Большинство наших товаров имеются в наличии на складе; в случае отсутствия необходимой позиции мы обеспечим её поставку под заказ.
После оформления заказа наши менеджеры оперативно свяжутся с вами для уточнения деталей оплаты и наиболее удобных вариантов доставки.
Преимущества
нашего магазина
Доставка по всей РФ
Точки самовывоза в Москве, курьерская доставка, отправка транспортными компаниями.
Лучшие цены
Мы являемся официальными дистрибьюторами и дилерами ведущих мировых брендов.
20+ лет на рынке
Мы работаем с 1998 года и поставляем только качественное оборудование.