| Basic function | Residual current circuit-breakers |
| Number of poles | 4 pole |
| Application | Residual current circuit-breaker for residential and commercial applications |
| Rated current [In] | 25 A |
| Rated short-circuit strength [Icn] | 6 kA |
| Rated fault current [IΔN] | 0.1 A |
| Type | Type A |
| Tripping | non-delayed s… |
| Product range | CFI6 |
| Sensitivity | Pulse-current sensitive |
| Impulse withstand current | Partly surge-proof 250 A |
| Electrical | |
| Standards | IEC/EN 61008 |
| Rated operational voltage [Ue] [Ue]Rated operating voltage [Ue] | 230/400 V AC |
| Rated frequency [f] | 50 Hz |
| Limit values of the operating voltage Test circuit | 196 - 456 V AC |
| Sensitivity | Pulse-current sensitive |
| Rated insulation voltage [Ui ] | 440 V |
| Rated impulse withstand voltage [Uimp] | 4 kV |
| Rated short-circuit strength [Icn] | 6 kA |
| Rated making and breaking capacity / Rated residual making and breaking capacity [Im / IΔm] | 500 A |
| lifespanElectrical [Operations] | ≧ 4000 |
| lifespanMechanical [Operations] | ≧ 20000 |
| References | |
| Auxiliary switch for subsequent installation | Z-HK 248432 |
| Remote tripping module | Z-FAM 248293 |
| Sealing cover set | Z-RC/AK-4TE 101062 |
| Mechanical | |
| Standard front dimension | 45 мм |
| Device height | 80 мм |
| Built-in width | 70 (4TE) mm |
| Mounting | Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 |
| Degree of Protection | IP40 enclosed |
| Terminals top and bottom | Open mouthed/lift terminals |
| Terminal protection | finger and hand touch safe, DGUV VS3, EN 50274 |
| Terminal cross-sectionSolid | 1.5 - 35 mm2 |
| Terminal cross-sectionStranded | 2 x 16 mm2 |
| Thickness of busbar material | 0.8 - 2 mm |
| Permissible storage and transport temperatures | -35 - +60 °C |
| Climatic proofing | 25-55°C/90-95% relative humidity according to IEC 60068-2 |
| Thickness of busbar materialMaterial thickness | 0.8 - 2 mm |
| Technical data for design verification | |
| Rated operational current for specified heat dissipation [In] | 25 A |
| Heat dissipation per pole, current-dependent [Pvid] | 0 W |
| Equipment heat dissipation, current-dependent [Pvid] | 2.8 W |
| Static heat dissipation, non-current-dependent [Pvs] | 0 W |
| Heat dissipation capacity [Pdiss] | 0 W |
| Operating ambient temperature min. | -25 °C |
| Operating ambient temperature max. | +55 °C |
| Starting at 40 °C, the max. permissible continuous current decreases by 3% for every 1 °C | |
| IEC/EN 61439 design verification | |
| 10.2 Strength of materials and parts10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2 Strength of materials and parts10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2 Strength of materials and parts10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2 Strength of materials and parts10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9 Insulation properties10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9 Insulation properties10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003) | |
| Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB) (ecl@ss10.0.1-27-14-22-01 [AAB906014]) | |
| Number of poles | 4 |
| Rated voltage | 400 V |
| Rated current | 25 A |
| Rated fault current | 100 mA |
| Rated insulation voltage Ui | 440 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Mounting method | DIN rail |
| Leakage current type | A |
| Selective protection | No |
| Short-time delayed tripping | No |
| Short-circuit breaking capacity (Icw) | 6 kA |
| Surge current capacity | 0.25 kA |
| Frequency | 50 Hz |
| Additional equipment possible | Yes |
| With interlocking device | Yes |
| Degree of protection (IP) | IP20 |
| Width in number of modular spacings | 4 |
| Built-in depth | 69.5 мм |
| Ambient temperature during operating | -25 - 40 °C |
| Pollution degree | 2 |
| Connectable conductor cross section multi-wired | 1.5 - 16 mm² |
| Connectable conductor cross section solid-core | 1.5 - 35 mm² |
На этой странице вы можете приобрести Eaton Устройство защитного отключения, 4 полюса, тип А, 25А, 100мА (артикул: 0000235781). Мы рекомендуем внимательно изучить представленные технические характеристики и ознакомиться с официальными брошюрами от Eaton, чтобы выбрать товар в нужной конфигурации.
Для покупки модели CFI6-25/4/01-A-DE просто нажмите кнопку «В корзину» и перейдите в корзину для оформления заказа. Большинство наших товаров имеются в наличии на складе; в случае отсутствия необходимой позиции мы обеспечим её поставку под заказ.
После оформления заказа наши менеджеры оперативно свяжутся с вами для уточнения деталей оплаты и наиболее удобных вариантов доставки.
Точки самовывоза в Москве, курьерская доставка, отправка транспортными компаниями.
Мы являемся официальными дистрибьюторами и дилерами ведущих мировых брендов.
Мы работаем с 1998 года и поставляем только качественное оборудование.